This manual provides detailed instructions for the installation, operation, and maintenance of the QOLTEC 50900 Three Phase Electronic Energy Consumption Meter. This device is designed for measuring active energy consumption in three-phase, four-wire AC circuits. Please read this manual thoroughly before installation and use to ensure proper function and safety.

2. უსაფრთხოების ინფორმაცია

გაფრთხილება: Installation and maintenance of this device must be performed by qualified personnel only. Failure to follow these instructions can result in electric shock, fire, or serious injury.

3. პროდუქტი დასრულდაview

The QOLTEC 50900 is a compact, DIN rail mountable electronic energy meter designed for accurate measurement of three-phase energy consumption. It features an LCD display for clear readings and a pulse output for remote monitoring.

QOLTEC 50900 Energy Meter with dimensions and key features

Figure 3.1: QOLTEC 50900 Energy Meter showing dimensions (75mm x 92mm x 76mm) and key features like Three Phase Type, 230V Rated Voltage, 1.0 Precision Class, and LCD Display.

ძირითადი მახასიათებლები:

4. სპეციფიკაციები

პარამეტრიღირებულება
მოდელი50900
რეიტინგული ტომიtage3x230/400V AC
რეიტინგული მიმდინარე3x10(100)A
სიხშირე50 ჰც
სიზუსტის კლასი1.0
ჩვენებაLCD
პულსის გამომუშავება400 imp/kWh
ინსტალაციაDIN Rail (4P)
ზომები (W x H x D)75 x 92 x 76 მმ
წონა100 გ
მასალააკრილის

5. დაყენება და ინსტალაცია

The QOLTEC 50900 meter is designed for standard 35mm DIN rail mounting. Ensure the installation location is dry, well-ventilated, and free from excessive vibration or electromagnetic interference.

5.1 მონტაჟი

  1. ელექტრო პანელში იპოვეთ შესაბამისი 35 მმ-იანი DIN რელსი.
  2. Align the meter's DIN rail clip with the rail.
  3. Press the meter firmly onto the rail until it clicks into place.
QOLTEC 50900 Energy Meter mounted on a DIN rail

Figure 5.1: The QOLTEC 50900 meter securely mounted on a DIN rail, showing its compact form factor.

5.2 გაყვანილობის კავშირები

მნიშვნელოვანია: All wiring must comply with local electrical codes and regulations. Ensure power is OFF before making any connections.

  1. Identify the input (IN) and output (OUT) terminals on the meter.
  2. Connect the incoming three-phase lines (L1, L2, L3) and Neutral (N) to the corresponding IN terminals (typically 5, 6, 7, 8).
  3. Connect the outgoing three-phase lines (L1, L2, L3) and Neutral (N) to the corresponding OUT terminals (typically 1, 2, 3, 4).
  4. დარწმუნდით, რომ ყველა შეერთება მჭიდრო და უსაფრთხოა, რათა თავიდან აიცილოთ კონტაქტების ფხვიერი კონტაქტები და გადახურება.
Wiring diagram for QOLTEC 50900 Energy Meter showing input and output terminals

სურათი 5.2: მხარე view of the meter showing the wiring diagram for input (IN) and output (OUT) connections for L1, L2, L3, and Neutral.

Front and terminal views of QOLTEC 50900 Energy Meter

სურათი 5.3: წინა view of the meter with its LCD display and a separate view of the terminal block for wiring connections.

6. საოპერაციო ინსტრუქციები

Once properly installed and powered, the QOLTEC 50900 meter will automatically begin measuring energy consumption.

6.1 LCD ეკრანი

The LCD displays the total active energy consumption in kilowatt-hours (kWh). The display is continuous and does not require any button presses for basic reading.

Close-up of QOLTEC 50900 LCD display showing energy reading

სურათი 6.1: ახლოდან view of the LCD display showing an example energy reading in kWh.

6.2 პულსის გამომავალი

The meter features a pulse output (400imp/kWh) which can be used to connect to external monitoring systems for remote data collection. Refer to the external system's documentation for connection details.

7. მოვლა

The QOLTEC 50900 energy meter is designed for maintenance-free operation under normal conditions.

8. Დიაგნოსტიკა

If you encounter issues with your QOLTEC 50900 meter, refer to the following common problems and solutions:

პრობლემაშესაძლო მიზეზიგამოსავალი
No display/Meter not powering onNo power supply; Incorrect wiring; Blown fuse in circuitCheck power supply to the meter. Verify wiring connections. Check circuit breaker/fuse.
Incorrect energy readingIncorrect wiring; Faulty meterVerify wiring connections against the diagram. If wiring is correct, contact support.
Pulse output not workingIncorrect connection to external system; Faulty meterCheck pulse output wiring to the external system. Consult external system's manual. If issue persists, contact support.

If the problem persists after attempting these solutions, please contact Qoltec customer support.

9. გარანტია და მხარდაჭერა

Qoltec products are manufactured to high-quality standards. For warranty information and technical support, please refer to the warranty card included with your product or visit the official Qoltec webსაიტი. შეინახეთ თქვენი შესყიდვის ქვითარი შეძენის დასადასტურებლად.